Changes for page MTCA ADCs

Last modified by sndueste on 2024/07/08 09:50

From version 1.1
edited by sendels
on 2019/05/09 14:53
Change comment: There is no comment for this version
To version 3.1
edited by sendels
on 2019/05/09 14:55
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -1,0 +1,158 @@
1 +=== General info ===
2 +
3 +\\
4 +
5 +* [[ADQ412 server description~[~[image:url:http://hasfweb.desy.de/pub/TWiki/TWikiDocGraphics/external-link.gif~|~|width="13" height="12"~]~]>>url:https://ttfinfo.desy.de/FLASHWiki/Wiki.jsp?page=SPdevicesDMA%20ADQ||shape="rect"]]
6 +* [[more ADC server descriptions~[~[image:url:http://hasfweb.desy.de/pub/TWiki/TWikiDocGraphics/external-link.gif~|~|width="13" height="12"~]~]>>url:https://ttfinfo.desy.de/DOOCSWiki/Wiki.jsp#section-C_2B_2B+Server+Interface-D_ADCscope?page=C%2B%2B%20Server%20Interface||shape="rect"]]
7 +* [[Description of the DAQ properties related to the ADCs~[~[image:url:http://hasfweb.desy.de/pub/TWiki/TWikiDocGraphics/external-link.gif~|~|width="13" height="12"~]~]>>url:https://ttfinfo.desy.de/DOOCSWiki/Wiki.jsp#section-C_2B_2B+Server+Interface-DaqfedConfiguration.?page=C%2B%2B%20Server%20Interface||shape="rect"]]
8 +* [[ a collection of usefull things related to the OPIS ADCs>>doc:FLASHUSER.OPIS ADC related things]]
9 +
10 +\\
11 +
12 +=== Our cards ===
13 +
14 +\\
15 +
16 +==== SP-Devices ADQ412AC ====
17 +
18 +We have ADQ412AC-4G-MTCA digitizer cards for the experiment crates (Exp1, Exp2 and FL2Exp1):
19 +[[ADQ412_datasheet.pdf>>url:http://hasfweb.desy.de/pub/Setup/MtcaAdc/10-0494_C_ADQ412_datasheet.pdf||shape="rect"]] ( [[new version>>url:http://hasfweb.desy.de/pub/Setup/MtcaAdc/10-0494-adq412_datasheet.pdf||shape="rect"]], [[sampling rates table>>url:http://hasfweb.desy.de/pub/Setup/MtcaAdc/Clocking_AppNote.pdf||shape="rect"]])
20 +The cards are connected via Patch panels to the Experimental endstations.
21 +
22 +\\
23 +
24 +* **NOTE: between ADC and Patch panel we have installed an [[EMP protector>>url:http://hasfweb.desy.de/pub/Setup/MtcaAdc/EMP_protector.pdf||shape="rect"]] and an additional 1dB attenuator**
25 +* for the influence of the Patch cable and the EMP protector see also [[this logbook entry~[~[image:url:http://hasfweb.desy.de/pub/TWiki/TWikiDocGraphics/external-link.gif~|~|width="13" height="12"~]~]>>url:http://ttfinfo.desy.de/ExpHallelog/show.jsp?dir=/2016/27/08.07&pos=2016-07-08T17:41:07||shape="rect"]]
26 +* we can offer amplifiers to either amplify small signals or to decouple setups which may deliver voltage peaks fro the ADCs. The available ADCs are:
27 +** 20 dB, 1 GHz, 50 Ohm, ( [[Minicircuits ZFL-1000LN+>>url:http://hasfweb.desy.de/pub/Setup/MtcaAdc/ZFL-1000LN.pdf||shape="rect"]])
28 +** 10 dB, 1.8 GHz, 50 Ohm, ( [[Becker und Hickl, ACA-1-10-I>>url:http://hasfweb.desy.de/pub/Setup/MtcaAdc/ACA-amilifier.pdf||shape="rect"]])
29 +
30 +\\
31 +
32 +\\
33 +
34 +* [[Here is a detailed evaluation >>url:http://hasfweb.desy.de/pub/Setup/MtcaAdc/Output_behaviour_of_Mini-Circuits_Amplifier.pdf||shape="rect"]]of the 2 amplifiers , their linearity and influence on the signal broadening for different input signals*
35 +* And the test of the [[Philips scientific Model 6954>>url:http://hasfweb.desy.de/pub/Setup/MtcaAdc/Model_6954_Amplifier_Report.pdf||shape="rect"]]
36 +
37 +\\
38 +
39 +\\
40 +
41 +(% class="wrapped" %)
42 +|(((
43 +Impedance AC
44 +)))|(((
45 +50 OHM
46 +)))
47 +|(((
48 +Input voltage range
49 +)))|=(((
50 +800 mV pp!!!!!!!!!!!!!!!!
51 +)))
52 +|(((
53 +Digitizer resolution
54 +)))|(((
55 +12 bit
56 +)))
57 +
58 +4 CHANNELS MODE
59 +
60 +(% class="wrapped" %)
61 +|(((
62 +Sampling rate
63 +)))|(((
64 +2
65 +)))|(((
66 +GSPS
67 +)))
68 +|(((
69 +Analog bandwidth
70 +)))|(((
71 +2
72 +)))|(((
73 +GHz
74 +)))
75 +
76 +2 CHANNELS MODE
77 +
78 +(% class="wrapped" %)
79 +|(((
80 +Sampling rate
81 +)))|(((
82 +4
83 +)))|(((
84 +GSPS
85 +)))
86 +|(((
87 +Analog bandwidth
88 +)))|(((
89 +1.3
90 +)))|(((
91 +GHz
92 +)))
93 +
94 +\\
95 +
96 +===== ADC and DOOCS / DAQ =====
97 +
98 +The HDF5 names for the ADC traces are depending on the beamline :
99 +\\PG Beamline:
100 +{{code language="none"}}/FL1/Experiment/PG/ADQ412 GHz ADC/CH00/TD{{/code}}
101 +{{code language="none"}}/FL1/Experiment/PG/ADQ412 GHz ADC/CH01/TD{{/code}}
102 +{{code language="none"}}/FL1/Experiment/PG/ADQ412 GHz ADC/CH02/TD{{/code}}
103 +{{code language="none"}}/FL1/Experiment/PG/ADQ412 GHz ADC/CH03/TD{{/code}}
104 +
105 +BL Beamlines:
106 +{{code language="none"}}/FL1/Experiment/BL1/ADQ412 GHz ADC/CH00/TD{{/code}}
107 +{{code language="none"}}/FL1/Experiment/BL1/ADQ412 GHz ADC/CH01/TD{{/code}}
108 +{{code language="none"}}/FL1/Experiment/BL1/ADQ412 GHz ADC/CH02/TD{{/code}}
109 +{{code language="none"}}/FL1/Experiment/BL1/ADQ412 GHz ADC/CH03/TD{{/code}}
110 +\\{{code language="none"}}/FL1/Experiment/BL2/ADQ412 GHz ADC/CH00/TD{{/code}}
111 +{{code language="none"}}/FL1/Experiment/BL2/ADQ412 GHz ADC/CH01/TD{{/code}}
112 +\\{{code language="none"}}/FL1/Experiment/BL3/ADQ412 GHz ADC/CH02/TD{{/code}}
113 +{{code language="none"}}/FL1/Experiment/BL3/ADQ412 GHz ADC/CH03/TD{{/code}}
114 +
115 +DOOCS prop : {{code language="none"}}FLASH.FEL/ADC.ADQ.PG/EXP1.CH00/CH00.TDĀ  or CH00.DAQ.TD{{/code}}
116 +here the {{code language="none"}}CH00.TD{{/code}} is the full ADC trace as it is sampled ( typically several 100.000 samples per pulse train) while the {{code language="none"}}CH00.DAQ.TD{{/code}} trace only has the number of samples which are sent to the DAQ OR if //grouping// is actvated the {{code language="none"}}CH00.DAQ.TD{{/code}} contins only the grouped spectra. To read the ADC trace with an online analysis program the {{code language="none"}}CH00.DAQ.TD{{/code}} is preferable to use ...
117 +DAQ channel: {{code language="none"}}FLASH.FEL/ADC.ADQ.PG/EXP1.CH00{{/code}}
118 +
119 +in addition there are also additional parameters saved like:
120 +
121 +* sample frequency (in MHz)
122 +* error (state)
123 +* offset
124 +
125 +\\
126 +
127 +==== Struck SIS8300-L2D ====
128 +
129 +There is one in each of the MTCAs in the hall: MTCA-EXP1 at PG/BL1, the other at BL2 and BL3.
130 +
131 +They are 16 bit, 10 channel, 125 MS/s ADCs.
132 +
133 +\\
134 +
135 +* [[User Manual SIS8300-L2 ADC ACM>>url:http://hasfweb.desy.de/pub/Setup/MtcaAdc/sis8300l2-m-x009-1-v101.pdf||shape="rect"]]
136 +* [[User Manual SIS8900 RTM>>url:http://hasfweb.desy.de/pub/Setup/MtcaAdc/sis8900-m-1-1-v104.pdf||shape="rect"]]
137 +
138 +50 Ohm input impedance, -1 V,...,+1 V default input range, analog signals can be routed to AC and DC input stage. The coupling is DC via op-amp (switching to AC transformer involves resoldering of SMD solder bridges).
139 +
140 +Here is a trace of the first signal, a 1 MHz trigger connected from the x2timer board in the same MTCA:
141 +
142 +[[image:url:http://hasfweb.desy.de/pub/Setup/MtcaAdc/adc_mhz.jpg||alt="adc_mhz.jpg" width="550" height="500"]]
143 +
144 +\\
145 +
146 +==== Using the Struck SIS8300-L2D to detect only integrated values of pulses ====
147 +
148 +FS-LA (Falko Peters) programmed a pulse detection server that automatically detects peaks in the signel and integrates the samples around the peak. <\br> things to set:
149 +
150 +* Peak height: from what signal on (incounts) is the signal to be counted as peak
151 +* pre and post peak integration time: how much ns to be integrated before and after the peak sample that are taken into account for the peak
152 +* pre and post peak noise time: before and after the samples that are taken for the actual signal these samples are used as background ( they also can be used to define the "deadtime" of the detector before it searches for new peaks.
153 +
154 +[[image:url:http://hasfweb.desy.de/pub/Setup/MtcaAdc/pulse_energy_server.jpg||alt="pulse_energy_server.jpg" width="400" height="300"]]
155 +
156 +\\
157 +
158 +* [[Model_6954_Amplifier_Report.pdf>>url:http://hasfweb.desy.de/pub/Setup/MtcaAdc/Model_6954_Amplifier_Report.pdf||shape="rect"]]: Model_6954_Amplifier_Report.pdf