Changes for page Trigger Howto
Last modified by sndueste on 2023/07/07 11:28
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -10,7 +10,10 @@ 10 10 In short: 11 11 12 12 * the triggers are for low impedance (~~50 Ohm ) 13 -* signal level is + 5V - otherwise 0V (in the expert panel one can also invert the signal - base line is +5 V and trigger 0V) 13 +* signal level is: 14 +** + 3 V to + 4.5V for high (actual trigger) and 0V for low (baseline) at 50 Ohm 15 +** + 6 V to + 9V for high and 0V for low at 1 MOhm 16 +** one can also invert the signal in the expert panel ( thus the base line is + (3-5) V and the actual trigger signal is 0V) 14 14 * The trigger are send to the MTCA several ms before the first FEL pulse (3.1 ms for the "standard" trigger, 21.5 ms for the "early" trigger). 15 15 * The timer card can delay the trigger in 9 ns steps for more than 100 ms (an option to shift the trigger in 1 ns steps is available in the expert panel) 16 16 * The shown delay in µs is in respect to the //first// FEL pulse. negative delay: trigger comes before FEL, positive : trigger comes after the FEL.