10 10  In short:
11 11  
12 12  * the triggers are for low impedance (~~50 Ohm )
13 -* signal level is + 5V - otherwise 0V (in the expert panel one can also invert the signal - base line is +5 V and trigger 0V)
13 +* signal level is:
14 +** + 3 V to + 4.5V  for high (actual trigger)  and  0V for low (baseline) at 50 Ohm
15 +** + 6 V to + 9V  for high  and  0V for low at 1 MOhm
16 +** the different trigger levels come from different hardware versions of the trigger hardware ... (4.5 V new, 3 V old)
17 +** one can also invert the signal in the expert panel ( thus the base line is + (3-5) V and the actual trigger signal is  0V)
14 14  * The trigger are send to the MTCA several ms before the first FEL pulse (3.1 ms for the "standard" trigger, 21.5 ms for the "early" trigger).
15 15  * The timer card can delay the trigger in 9 ns  steps for more than 100 ms (an option to shift the trigger in 1 ns steps is available in the expert panel)
16 16  * The shown delay in µs is in respect to the //first// FEL pulse. negative delay: trigger comes before FEL, positive : trigger comes after the FEL.
... ... @@ -322,6 +322,12 @@
322 322  
323 323  \\
324 324  
329 += Some expert infos =
330 +
331 +== how to find details (age ...) of the timer cards / RTMs ==
332 +
333 +[[image:attach:Capture.PNG||height="250"]][[image:attach:Capture1.PNG||height="250"]][[image:attach:Capture2.PNG||thumbnail="true" height="250"]]
334 +
325 325  \\
326 326  
327 327  \\
... ... @@ -329,3 +329,7 @@
329 329  \\
330 330  
331 331  \\
342 +