... ... @@ -10,11 +10,7 @@
10 10  In short:
11 11  
12 12  * the triggers are for low impedance (~~50 Ohm )
13 -* signal level is:
14 -** + 3 V to + 4.5V  for high (actual trigger)  and  0V for low (baseline) at 50 Ohm
15 -** + 6 V to + 9V  for high  and  0V for low at 1 MOhm
16 -** the different trigger levels come from different hardware versions of the trigger hardware ... (4.5 V new, 3 V old)
17 -** one can also invert the signal in the expert panel ( thus the base line is + (3-5) V and the actual trigger signal is  0V)
13 +* signal level is + 5V - otherwise 0V (in the expert panel one can also invert the signal - base line is +5 V and trigger 0V)
18 18  * The trigger are send to the MTCA several ms before the first FEL pulse (3.1 ms for the "standard" trigger, 21.5 ms for the "early" trigger).
19 19  * The timer card can delay the trigger in 9 ns  steps for more than 100 ms (an option to shift the trigger in 1 ns steps is available in the expert panel)
20 20  * The shown delay in µs is in respect to the //first// FEL pulse. negative delay: trigger comes before FEL, positive : trigger comes after the FEL.
... ... @@ -326,12 +326,6 @@
326 326  
327 327  \\
328 328  
329 -= Some expert infos =
330 -
331 -== how to find details (age ...) of the timer cards / RTMs ==
332 -
333 -[[image:attach:Capture.PNG||height="250"]][[image:attach:Capture1.PNG||height="250"]][[image:attach:Capture2.PNG||thumbnail="true" height="250"]]
334 -
335 335  \\
336 336  
337 337  \\
... ... @@ -339,7 +339,3 @@
339 339  \\
340 340  
341 341  \\
342 -
343 -\\
344 -
345 -\\